LAUDA heating and cooling systems from the secondary circuit unit line of the KP series (Kryopac) always consist of the circulation pump, expansion vessel, electric heater modules and the special Kryopac system - a heat exchanger that was specially developed to vaporize liquid nitrogen. With this system, you can control low-temperature reactions reliably. This heating technology comes from the proven modular system of the heat transfer units. The Kryopac units produce a temperature-controlled liquid flow and are delivered as a compact, fully insulated, ready-to-connect system with control cabinet, completely pre-tested at the factory. Freezing problems in the heat exchangers are a thing of the past. Standard heat carriers can be cooled down virtually to the solidifying point. The LAUDA technology makes it possible to approach this point precisely to the degree. Compact set-up, high safety standard and low price are additional benefits of the Kryopac systems.
Technical data for the Kryopac type series
Features | KP 150 (Ex) | KP 250 (Ex) | KP 350 (Ex) | KP 400 (Ex) | KP 600 (Ex) |
---|---|---|---|---|---|
Heat carriers | Thermal oil, special liquids | ||||
Working temperature (°C) | - 150 ... 280 | ||||
Pump output (m³/h) | 0.5 … 2 | 2 … 4 | 4 … 10 | 10 … 30 | 30 ... 80 |
Electrical heating output (kW) | 3 ... 6 | 9 ... 12 | 18 ... 50 | 60 ... 100 | 125 ... 500 |
Cooling output at - 100 °C (kW) | up to 5 | up to 10 | up to 15 | up to 30 | up to 80 |
Min. dimension (mm) | 500 x 100 x 1500 | 600 x 1500 x 1500 | 800 x 1700 x 1500 | 1000 x 1500 x 1900 | 1500 x 2200 x 2000 |
Max. dimension (mm) | 600 x 1500 x 1500 | 800 x 1700 x 1500 | 1000 x 1500 x 1900 | 1300 x 1900 x 2000 | 2000 x 2500 x 2000 |